The compact head mounted temperature transmitter type from ABB is designed for standard type B sensor heads. The advantage increased measuring accuracy resulting from conversion of the sensor signal into a stable output signal close to the sensor. When using thermocouples, no compensating cables are therefore required.
Offerings.
TTF200
The TTF200 HART temperature transmitter completes the TTx200 / TTx300 product family in proven two-wire technology.
Data
- Universal sensor input
– RTD, thermocouple, Ω, mV - Functional safety SIL 2 / SIL 3 in accordance with IEC 61508
- Output signal
– 4 to 20 mA, HART - Accuracy 0.1 %, long-term stability 0.05 % per year
- Wire break / corrosion monitoring in accordance with NE 89
- Diagnostic information in accordance with NE 107
- IP 66 / IP 67, NEMA 4X aluminum or stainless steel field-mount housing
- Large, user-friendly LCD indicator Type BS
- Approvals for explosion protection
– ATEX, IECEx, zone 0
TTH300
The two-channel temperature transmitter TTH300 with HART, PROFIBUS PA or FOUNDATION Fieldbus in two-wire technology has extensive functions and diagnostic options for all applications. For the new TTH300 HART, these have been expanded once again and the user-friendliness has been further improved.
Data
- Two universal sensor inputs, each for RTD, thermocouple, Ω, mV
- Functional safety SIL 2 / SIL 3 in accordance with IEC 61508 (HART variant)
- Various sensor error-calibration possibilities
– One point, two point, Callendar-van-Dusen, freestyle characteristics with 32 supporting points - Sensor backup / automatic sensor redundancy switching (2 x Pt100 3-wire connection and further sensor combinations)
- Redundancy behavior configurable for increased availability, increased safety or increased accuracy (HART variant)
- Output signal
– 4 to 20 mA, HART 5 and HART 7 (switchable)
– PROFIBUS PA 3.01
– FOUNDATION Fieldbus ITK 5.x - Accuracy 0.1 %, long-term stability 0.05 % per year
- Wire break / corrosion monitoring in accordance with NE 89
- Device status signaling and freely configurable diagnostic categorization with diagnostic history according to NE 107 (HART variant)
- Event monitor for logging critical events (HART variant)
- Configuration monitor for configuration changes (HART variant)
- Turnable LCD indicator with operating buttons (option)
- Approvals for explosion protection
– ATEX, IECEx, zone 0
– FM / CSA
– EAC, EAC-Ex
– NEPSI